General Information 

When assessing an existing structure for potential damaging effects, two factors must be  considered. These are movement of structural components in relation to one another and material  deterioration. Material volume changes, mostly from ambient daily and seasonal temperature  changes, as well as potential long-term deflections, are likely to be the most significant. Any and  all foundation movements can be important such as those caused by settling of the soil beneath the  structure. However, upward movement owing to expansive soils may also occur. If built on deep  unconsolidated fine grained or cohesive soils, or from subterranean losses or movements from a  variety of reasons, buildings on spread footings may demonstrate continuous, even recent  settlements.  

General Information 

Building materials deteriorate solely in the presence of moisture, with the exception of  metals and their natural inclination to revert to the oxide form throughout the corrosive process.  Extremely hostile circumstances persist all year in this oceanic climate due to the high salinity of  the environment. Outside relative humidity can be as high as 90 or 95 percent for much of the  year, whereas relative humidity inside air-conditioned buildings is usually about 35 to 60 percent.  Moisture vapor pressures of around 1/3 to 1/2 pound per square inch will exist much of the time  under these conditions. Moisture vapor will move to locations with lower pressure. Even at  relatively low pressures, building materials like stucco, masonry, and even concrete remain  permeable. Condensation will occur within the enclosed walls of the structure because most of  our local construction does not use vapor barriers. As a result, damage is more likely to be found  along outside walls or any locations where moisture or direct leakage has been allowed to enter  the building envelope.  

Over time, deterioration of building materials will continue to occur and may necessitate  repair work to be performed. The type of repair will be determined by the role of the member or  component in the structural system as well as the degree of deterioration. In non-sensitive parts  of the structure like tie beams and columns, cosmetic repairs may be sufficient if the residual 

material is sufficient for the needed function and appears to be satisfactory to good condition.  Cosmetic type repairs shall only be allowed on members carrying assigned gravity or other loads  if it can be shown that the remaining material, if safeguarded from further deterioration, can still  perform its intended function at acceptable stress levels. In the event that this is not possible,  repairs or reinforcement of the structure or component will be required.  

Sound testing, when conducted as required, is used to help determine the defective areas  in the reinforced concrete foundations, slabs, walls, and columns. Sounding is a simple, non destructive test typically accomplished with a metal hammer or steel rod by simply striking the  tool head on the surface and listening to the resulting sound. Solid concrete will produce a sharp  distinct ringing sound that the area is intact and solid. Spalled, cracked, delaminated, or voided  concrete will produce a flat or dull sound. Sound testing is best suited for flat surfaces, vertical or  horizontal, where large areas can be tested and evaluated in a reasonable amount of time. 

Inspection 

Our engineers inspected the building on-site including eleven (11) residential units and  three (3) roof attics as per Table 1, in addition to building envelope, mechanical and elevator  rooms, elevator pits, and carports. These inspections consisted solely of visual means with no  destructive testing and was thoroughly executed throughout the entire living area inside the units,  with particular attention to all load-bearing walls and the primary structural members and systems,  including components beams, columns, and slabs, along with doors and windows water tightness.  The exterior of the building was also thoroughly inspected by visual means with particular  attention to the concrete, stucco, and steel components, as well as the waterproofing condition of  roof. 

Table 1. Inspected units and roof attic at Cypress Glen 3 

When performed in a systematic manner, visual examination will be regarded as adequate  in the vast majority of cases. The visual inspection must be carried out in all habitable and non habitable parts of the building, as determined by the inspecting expert, in order to ensure  compliance. Surface flaws such as fractures, distortion, sagging, severe deflections, considerable  misalignment, leakage evidence, and peeling of stucco, if present, should be taken seriously as  indicators of potential damages that may necessitate repair work. The methods of inspections used  included line-of-sight damage spotting and light tapping with a hammer, sounding, on concrete  surfaces suspected of being presently damaged in some capacity. 

Observed Conditions 

Overall, the building is structurally sound and in good condition. Significant deterioration  in terms of cracking or spalling of the slabs, beams, and columns or movement of such components  such as due to settlement was not observed during our inspection. Regarding specific observations  documented during our inspection of each component, these conditions are discussed as follows. 

Residential Units and Roof Attics 

  • All doors and windows in the residential units inspected appear to be in satisfactory  condition and functioning as intended as shown in Figures 3 thru 8.  
  • Wood roof trusses and framing appear to be in good condition as shown in Figures 9 thru 12. 
  • Horizontal stucco crack on ceiling of bedroom in Unit 319 and 324 as shown in Figure 13- 14. 
  • Sliding glass door movement in Units 309 and 312 as shown in Figure 15-16. • Window frame movement in Unit 312 as shown in Figure 17. 

Building Envelope  

  • All exterior sides of the building show no visible signs of deterioration nor damage as  shown in Figures 18 thru 21.  
  • All walkway areas on first, second, and third levels appear to be in good condition as shown  in Figures 22 thru 24.  
  • Walkway and stairwell on the second floor have cracked concrete at base of railing as  shown in Figure 25. 
  • Walkway and stairwell on the third floor have cracked concrete at base of railing as shown  in Figure 26.  
  • All three (3) stairways appear to be in good condition as shown in Figures 27 thru 29.  • Water stain on northeast elevation stairwell as shown in Figure 30. 

Service Rooms  

  • Elevator room appear to be in satisfactory condition as shown in Figures 31. 
  • Elevator pit had oil stains, dirt, and minor debris as shown in Figure 32. 
  • Bottom of the elevator area appears to be in satisfactory condition as shown in Figure 33.  

Carports 

  • Top and underside of roofs of both carport and garages appear to be in good condition as  shown in Figures 34 and 35. 
  • Metal framing and column posts for the carport and wooden truss for the garage appear to  be in good condition as shown in Figures 36 thru 38. 
  • Bent metal frame on column of carport as shown in Figure 39. 

Conclusion 

We completed our inspection and investigation of the residential building and its  components located at 3235 Cypress Glen Way in Naples, Florida. The overall structure of the  building as well as the roof, building envelope, mechanical rooms, and elevator pits, along with  the attached carport are all in structurally sound condition with no significant structural  deficiencies observed. As a matter of routine maintenance, we recommend every three (3) years  painting/sealing the bottom areas of all carport column posts on all sides at the base where they  meet the ground. These areas tend to rust and deteriorate over time. We recommend the following  minor repairs to the building.

  • Repair and seal horizontal stucco crack on balcony ceiling in Unit 319 and 324 as shown  in Figure 13-14. 
  • Repair sliding glass door frame movement in Unit 309 and 312 and preform maintenance  as shown in Figure 15-16. 
  • Repair window frame movement in Unit 316 and preform maintenance as shown in Figure  17. 
  • Repair sliding glass door frame movement in Unit 309 and 312 and preform maintenance  as shown in Figure 15-16. 
  • Fill and seal concrete cracks on stairwells and walkways on the second floor as shown in  Figure 25. 
  • Fill and seal concrete cracks on stairwells and walkways on the third floor as shown in  Figure 26. 
  • Repaint water stains on stairwell on northeast elevation as shown in Figure 30. • Repair bent metal frame on column of carport as shown in Figure 39. 

Cronin Engineering recommends that this minor repair work be done by a licensed  professional contractor in accordance with local building codes and laws. Attached are pictures  from our inspection. If you need additional information or have any further questions, please  contact our office.